Differential Pressure Flow Transmitter Calibration — Wet Leg vs Dry Leg

Practical Procedure · Calibration

Differential Pressure Flow Transmitter Calibration — Wet Leg vs Dry Leg

Applies to: Orifice plate, venturi, and other DP-based flow measurement using a differential pressure transmitter | Equipment needed: DP calibrator/pump (or two-point pressure source), HART communicator (if applicable), reference for leg fluid density (wet leg installations)

Before You Start

  • Confirm whether this is a dry leg or wet leg installation — this changes your entire approach, so check the P&ID or physically trace the impulse lines before touching anything.
  • Isolate the transmitter from the process using the 3-valve or 5-valve manifold, following your plant's isolation procedure.
  • Note the configured range from the nameplate or configuration (e.g., 0–500 mmH2O = 4–20 mA) and the square-root extraction setting if flow is derived from DP.
DP Flow Measurement: The Orifice Plate Principle
Flow speeds up through the restriction, creating a measurable pressure drop
DP
Transmitter
High side
Low side
The orifice plate forces fluid through a smaller opening, causing velocity to increase and pressure to drop on the downstream side. The transmitter measures this pressure difference (high side minus low side) and, after square-root extraction, converts it into a flow rate. This is why the "high" and "low" tap locations — and keeping their impulse lines correctly filled (wet leg) or dry — matter so much to calibration accuracy.

Step 1 — As-Found Check

  • With both isolation valves closed and the equalizing valve open, verify the transmitter reads zero DP (this is your zero reference before doing anything else).
  • Apply DP at 0%, 25%, 50%, 75%, and 100% of range using the calibrator, and record the transmitter's actual output at each point before adjusting anything.
  • Compare against tolerance — if all points are within spec, document and skip adjustment; if not, proceed to Step 2.

Step 2 — Zero Adjustment (Critical for Wet Leg)

  • For a wet leg installation, the static head of the fill fluid in the impulse line creates a constant offset — this must be zeroed out with the process in its normal filled condition, not with the lines dry.
  • For a dry leg installation, zero can typically be done with both impulse lines at atmospheric/equal condition without needing to account for fluid head.
  • Adjust the zero setting until the transmitter reads exactly 0% output with zero differential applied under the correct leg condition.

Step 3 — Span Calibration

  • Apply DP at 100% of range using the calibrator.
  • Adjust the span setting until the transmitter outputs exactly 20 mA (or 100% of its configured digital range).
  • Re-check zero after span adjustment — the two interact, so a final zero-span-zero pass is standard practice.

Step 4 — Linearity Check

  • Re-apply DP at 25%, 50%, and 75% and confirm the output tracks correctly at each point — a transmitter can be perfect at zero and span but still non-linear in between.
  • If linearity is off but zero/span are correct, this usually points to a transmitter capsule issue rather than a simple calibration error.
Wet leg maintenance note: Wet leg fill fluid can evaporate, leak, or change density over time (especially with temperature swings), silently shifting your zero without any alarm. If a DP transmitter on a wet leg system drifts repeatedly at the same rate, check the fill fluid level and condition before assuming the transmitter itself is failing.

Common Mistakes to Avoid

  • Zeroing a wet leg transmitter with the legs empty/dry — this bakes in a permanent offset error once the process fills the legs again.
  • Forgetting the square-root extraction when checking flow values against DP calibration points — a DP calibration point doesn't map linearly to a flow value.
  • Not re-checking zero after span adjustment.
  • Ignoring impulse line blockage or partial plugging as a root cause when a transmitter reads correctly on the bench but wrong when reconnected to process.

This is a general field procedure — specifics vary by transmitter brand and plant calibration standards. Adjust to your own SOP where needed.

Comments

Popular posts from this blog

Belt weigh feeder Zero and Span Drift

Zirconia Oxygen Analyzer Reading Maximum O2

Control Valve Positioner Calibration